Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed
and started up only by a professional when used in the first environment.
Note: A professional is a person or organization having necessary skills in installing
and/or starting up power drive systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in
the second environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current
equal to or above 400 A, or intended for use in complex systems in the second
environment.
Category C1
The drive complies with the conducted emission limits of the standard with the following
provisions:
1.
The optional EMC filter is selected according to section External EMC
filters (page 150), and the filter is installed as specified in the EMC filter manual.
2. The motor and control cables are selected as specified in this manual. The EMC
recommendations are obeyed.
3. The maximum motor cable length does not exceed the specified maximum value.
See EMC compatibility and motor cable length (page 153).
4. The drive is installed according to the instructions given in this manual.
This product can cause radio-frequency inference. In a residential or domestic
environment, supplementary mitigation measures may be required in addition to the
requirements listed above for the CE compliance.
Category C2
This is applicable to drives with an internal EMC C2 filter.
The drive complies with the standard with the following provisions:
1. The motor and control cables are selected as specified in this manual. The EMC
recommendations are obeyed.
2. The maximum motor cable length does not exceed the specified maximum. See
EMC compatibility and motor cable length (page 153).
3. The drive is installed according to the instructions given in this manual.
This product can cause radio-frequency inference. In a residential or domestic
environment, supplementary mitigation measures may be required in addition to the
requirements listed above for the CE compliance.
160 Technical data