Rockwell Automation Publication 2711P-UM007D-EN-P - December 2015 19
Chapter 2
Install the PanelView Plus 7 Standard Terminal
The equipment meets the requirements of the standards and ratings that are
listed in Table 10
.
Table 10 - ATEX and INMETRO Ratings
Topic Page
Hazardous Locations 21
Considerations for Mounting 25
Clearances for Mounting 25
Panel Guidelines 26
Panel Cutout Dimensions 26
Prepare for Panel Mounting 27
Mount the Terminal in a Panel 30
Remove and Replace Power Terminal Block 34
Connect Power 35
Connect to a Network 36
Initial Startup 40
Reset the Terminal 40
ATTENTION: Do not use a PanelView™ Plus 7 Standard terminal for
emergency stops or other controls critical to the safety of personnel or
equipment. Use separate hard-wired operator interface devices that do not
depend on solid-state electronics.
ATEX:
EN 60079-0:2009, EN 60079-11:2012, EN 60079-15:2010,
and EN 60079-31:2009
II 3 GD
Ex ic nA IIC T4 Gc
Ex tc IIIC T135 °C (275 °F) Dc IP66
Tamb = 0 °C…+55 °C (32 °F…+131 °F)
DEMKO 14 ATEX 1302X
INMETRO:
ABNT NBR IEC 60079-0:2008+Errata 1:2011; ABNT
NBR IEC 60079-11:2009; ABNT NBR IEC 60079-
15:2012; e ABNT NBR IEC 60079-31:2011
Ex ic nA IIC T4 Gc
Ex tc IIIC T135 °C (275 °F) Dc IP66
Tamb = 0 °C to +55 °C (32 °F to +131 °F)
UL-BR 14.0716X