Operating i-Vu CCN Pro
22 i-Vu CCN Pro 4.2
○ Type a number in the Change All By field (c).
8 Click Set All To or Change All By.
9 Click Apply Changes.
NOTE To modify several properties in multiple control programs at the same time, use the Global Copy
feature.
Create stand-alone applications
In ApplicationBuilder, you can create some pre-engineered, stand-alone equipment applications with a view
for
Consumable Reports for Energy Meters (electric, gas, water, steam, generic), non-linear flow meters,
energy (BTU) consumption, and equipment runtime.
These options can be added to CCN Values Only and Link Integration custom equipments. Mapping the
points allows monitoring.
NOTES
• One meter and one Runtime may be added to equipment.
• There is an application for a CCN Vertical Pack unit. This is a CC with special software and BEST++.
While this controller can be discovered in i-Vu CCN Pro in
System Setup as a Vertical Pack, none of the
possible selected options can be auto-discovered at this time, so only a base view will be generated. This
application allows the Installer to generate a correct equipment and view file based on the selected
options.
Assign and download a custom UC/CC equipment file
1 In the i-Vu CCN Pro navigation tree, right-click on the equipment and select Configure from the drop-
down menu.