EasyManuals Logo
Home>Carrier>Control Systems>i-Vu CCN Pro 4.2

Carrier i-Vu CCN Pro 4.2 User Manual

Carrier i-Vu CCN Pro 4.2
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Monitor and control equipment
i-Vu CCN Pro 4.2 45
Setpoints
Programmed setpoints are set and changed by operators.
Effective setpoints reflect the impact of other system conditions on the programmed setpoints, such as
setpoint adjustments, and hysteresis. Effective setpoints control the equipment.
To change programmed setpoints:
1 Navigate to a setpoint control in one of the following places:
The Space Temperature Setpoints section of the Equipment tab of a Properties page
A Graphics page
2 On a programmed setpoint bar, click and drag the segment or the gap between segments you want to
change.
3 Type new values in the Heating and Cooling fields.
TIP You can click and drag a segment or a gap between segments to change setpoints.
4 Click OK.
To display or change driver or set driver properties
NOTE Only the Installer role has access to the following.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier i-Vu CCN Pro 4.2 and is the answer not in the manual?

Carrier i-Vu CCN Pro 4.2 Specifications

General IconGeneral
BrandCarrier
Modeli-Vu CCN Pro 4.2
CategoryControl Systems
LanguageEnglish

Related product manuals