FINAL DRAFT - CISCO CONFIDENTIAL
5-13
Cisco ONS 15216 EDFA2 Operations Guide
78-16033-01
Chapter 5 SNMP MIB Installation and Configuration
Tables and Groups
Use the snmp attribute set local cerent15216EdfaOpSaveConfig perform command to save changes.
cerent15216EdfaCLEI Display String
(0 to 10
characters)
Read-only Indicates the factory setting of the
Common Language Equipment
Identifier (CLEI) code (established by
Telcordia) of the Cisco
ONS 15216 EDFA2. This attribute
can be accessed but not changed by
the user.
cerent15216EdfaPowerBus
Mode
cerent15216Edfa
PowerBusMode
Read-write Simplex for one power source (Bus
A) or duplex for redundant power
source (Bus A and Bus B) Power Bus
mode.
cerent15216EdfaPowerBus
DCVoltageMin
Integer
(350 to 700)
Read-write Minimum allowable power bus DC
voltage. The default maximum power
bus voltage is set at –40 VDC. Valid
entries are between 350 and 700 and
are in negative volts times 10. For
example, if the voltage required is –40
VDC, the power bus setting is 400.
The power bus threshold has a 1.0V
tolerance and a 1.0V hysteresis. If the
minimum threshold is configured at
400 (-40 VDC), the alarm will not
raise until the voltage goes below -39
VDC and will not clear until the
voltage goes above -41 VDC.
cerent15216EdfaPowerBus
DCVoltageMax
Integer
(350 to 700)
Read-write Maximum allowable power bus DC
voltage. The default maximum power
bus voltage is set at –57 VDC. Valid
entries are between 350 and 700 and
are in negative volts times 10. For
example, if the voltage required is –57
VDC, the power bus setting is 570.
The power bus threshold has a 1.0V
tolerance and a 1.0V hysteresis. If the
maximum threshold is configured at
570 (-57 VDC), the alarm will not
raise until the voltage goes above -58
VDC and will not clear until the
voltage goes below -56 VDC.
Table 5-6 cerent15216EdfaCfgGroup Variable Descriptions (continued)
Variable Syntax
Maximum
Access Description

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco 15216 EDFA2 and is the answer not in the manual?

Cisco 15216 EDFA2 Specifications

General IconGeneral
BrandCisco
Model15216 EDFA2
CategoryNetwork Router
LanguageEnglish

Related product manuals