ED34-862 Specifications
FXMQ-P 245
7
2. Specifications
Ceiling Mounted Duct Type
Note:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5 m, level difference : 0 m.
3 External static pressure is changeable in 13 or 14 stages within the ( ) range by remote controller.
4 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
5 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7 Refer to page 255 for Fan Motor Input.
Model FXMQ20PVE FXMQ25PVE FXMQ32PVE
1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,200
Btu/h 7,800 9,900 12,600
kW 2.3 2.9 3.7
2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm 300×550×700 300×550×700 300×550×700
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch mm 3×16×1.75 3×16×1.75 3×16×1.75
Face Area 0.098 0.098 0.098
Fan
Model
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × Number
of Units
W 90×1 90×1 90×1
Air Flow Rate (HH/H/L)
m³/min 9/7.5/6.5 9/7.5/6.5 9.5/8/7
cfm 318/265/230 318/265/230 335/282/247
External Static
Pressure
Pa Standard 50 (100-30
3) Standard 50 (100-30 3) Standard 50 (100-30 3)
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Air Filter
4 4 4
Piping
Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection)
Gas Pipes mm
φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Drain Pipe mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Mass (Weight) kg 25 25 25
6 Sound Level (HH/H/L) dBA
220V 33/31/29 33/31/29 34/32/30
240V 33/31/29 33/31/29 34/32/30
Safety Devices
Fuse.
Fan Driver Overload Protector.
Fuse.
Fan Driver Overload Protector.
Fuse.
Fan Driver Overload Protector.
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable Outdoor Unit R-410A PA Series R-410A PA Series R-410A PA Series
Standard Accessories
Operation Manual. Installation Manual.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge
Flange. Air Suction Flange.
Operation Manual. Installation Manual.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge
Flange. Air Suction Flange.
Operation Manual. Installation Manual.
Drain Hose. Clamp Metal. Insulation
for Fitting. Sealing Pads. Clamps.
Washers. Screws. Air Discharge
Flange. Air Suction Flange.
Drawing No. C : 3D060388A
() () ()
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Все каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html

Table of Contents

Other manuals for Daikin VRV III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV III and is the answer not in the manual?

Daikin VRV III Specifications

General IconGeneral
TypeVRV (Variable Refrigerant Volume)
RefrigerantR410A
Energy EfficiencyHigh
ControlCentralized control systems, individual zone control
Operating Temperature Range (Cooling)-5°C to 46°C
Indoor Unit TypesCeiling Cassette, Ceiling Suspended, Wall Mounted, Floor Standing, Ducted
Power Supply380-415V, 50/60Hz, 3-Phase (depending on model)