Parameter 2-12 Brake Power Limit (kW)
Table 160: Parameter 2-12 Brake Power Limit (kW)
2-12 Brake Power Limit (kW)
Default value: Size related
Parameter type: Range, 0.001 - 2000.000 kW
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Parameter 2-12 Brake Power Limit (kW) is the expected average power dissipated in the brake resistor over a period of 120 s. It is used
as the monitoring limit for parameter 16-33 Brake Energy Average and thereby specifies when a warning/alarm is to be given. To
calculate parameter 2-12 Brake Power Limit (kW), the following formula can be used.
Pbr, avg W =
U
2
br V  × tbr s
Rbr Ω  × Tbr s
P
br,avg
is the average power dissipated in the brake resistor. R
br
is the resistance of the brake resistor. t
br
is the active braking time
within the 120 s period, T
br
. U
br
is the DC voltage where the brake resistor is active. This depends on the unit as follows:
T2 units: 390 V
T4 units: 810 V
T5 units: 810 V
T6 units: 943 V/1099 V for D–F enclosures
T7 units: 1099 V
N O T I C E
If R
br
is not known, or if T
br
is different from 120 s, the practical approach is to run the brake application, read parameter 16-33
Brake Energy Average and then enter this + 20% in parameter 2-12 Brake Power Limit (kW).
Parameter 2-13 Brake Power Monitoring
Table 161: Parameter 2-13 Brake Power Monitoring
2-13 Brake Power Monitoring
Default value: [0] Off
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
This parameter is only active in drives with a brake. This parameter enables monitoring of the power to the brake resistor. The pow-
er is calculated based on the resistance (parameter 2-11 Brake Resistor (ohm)), the DC-link voltage, and the resistor duty time. If pow-
er monitoring is set to [0] Off or [1] Warning, the brake function remains active, even if the monitoring limit is exceeded. This may
lead to thermal overload of the resistor. It is also possible to generate a warning via a relay/digital output. The measuring accuracy
of the power monitoring depends on the accuracy of the resistance of the resistor (better than ±20%).
Option
Name
Description
[0]*
Off
No brake power monitoring required.
[1]
Warning 120s
Activates a warning on the display when the power transmitted during the duty time exceeds
100% of the monitoring limit (parameter 2-12 Brake Power Limit (kW)). The warning disappears
when the transmitted power drops below 80% of the monitoring limit.
[2]
Trip 120s
Trips the drive and shows an alarm when the calculated power exceeds 100% of the monitoring
limit.
[3]
Warning & Trip 120s
Activates both of the above, including warning, trip, and alarm.
[4]
Warning 30s
[5]
Trip 30s
AU275636650261en-000101 / 130R0334 | 115Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals