Parameter 4-26 Power Limit Gener. Factor Source
Table 276: Parameter 4-26 Power Limit Gener. Factor Source
4-26 Power Limit Gener. Factor Source
Default value: [0] No function
Change during operation: True
Select the input that scales the value in parameter 4-83 Power Limit Generator Mode from 0% to 100%.
5.5.3 4-3* Motor Feedback Monitoring
This parameter group includes monitoring and handling of motor feedback devices, such as encoders and resolvers.
Parameter 4-30 Motor Feedback Monitoring Loss Function
Table 277: Parameter 4-30 Motor Feedback Loss Function
4-30 Motor Feedback Loss Function
Default value: Size related
Change during operation: True
This function is used to monitor consistency in the feedback signal, that is if the feedback signal is available. Select which action the
drive should take if a feedback fault is detected. The selected action is to take place when the feedback signal differs from the out-
put speed by the value set in parameter 4-31 Motor Feedback Speed Error for longer than the value set in parameter 4-32 Motor Feed-
back Loss Timeout.
AU275636650261en-000101 / 130R0334 | 159Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide