Parameter 6-53 Term 42 Output Bus Ctrl
Table 427: Parameter 6-53 Term 42 Output Bus Ctrl
6-53 Term 42 Output Bus Ctrl
Parameter type: Range, 0 - 100%
Change during operation: True
Holds the level of output 42 if controlled by bus.
Parameter 6-54 Term 42 Output Timeout Preset
Table 428: Parameter 6-54 Term 42 Output Timeout Preset
6-54 Term 42 Output Timeout Preset
Parameter type: Range, 0 - 100%
Change during operation: True
Holds the preset level of output 42. If a timeout function is selected in parameter 6-50 Terminal 42 Output, the output is preset to this
level if a fieldbus timeout occurs.
Parameter 6-55 Analog Output Filter
Table 429: Parameter 6-55 Analog Output Filter
6-55 Analog Output Filter
Change during operation: True
The following readout parameters from selection in parameter 6-50 Terminal 42 Output have a filter selected when parameter 6-55
Analog Output Filter is on.
Table 430: Readout Parameters
5.7.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for
analog common communication. Resolution on analog output is 12 bit.
AU275636650261en-000101 / 130R0334242 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide