5.23.3 30-5* Unit Configuration
N O T I C E
The following parameter is only available in FC 302:
Parameter 30-50 Heat Sink Fan Mode
Parameters in this group allow to configure the operation of internal units that communicate with the drive. The settings affect the
behavior of hardware components inside the drive.
Parameter 30-50 Heat Sink Fan Mode
Table 1087: Parameter 30-50 Heat Sink Fan Mode
Default value: Size related
Change during operation: True
Select how the heat sink fan responds to operating conditions. Use parameter 14-52 Fan Control to control the minimum fan speed.
The simple profile is a passive fan control based on the current temperature state of the drive. This
option represents the classic operating behavior of fans.
5.23.4 30-7* Power Low Monitor Protection
Parameter 30-70 Power Low Monitoring
Table 1088: Parameter 30-70 Power Low Monitoring
30-70 Power Low Monitoring
Default value: [0] Disabled
Change during operation: True
Disables the power-low monitoring feature.
Enables the power-low monitoring feature.
Parameter 30-71 PLM Detection Time
Table 1089: Parameter 30-71 PLM Detection Time
Parameter type: Range, 4 - 100 s
Change during operation: True
Set the detection time window for power integration.