Element in param-
eter 14-90 Fault
Level
1
In small and medium power drives, alarm 69, Power card temperature is only a warning.
2
Only high-power drives.
3
Warning 59 is configured in 1490.19. The current limit warning can be disabled by choice. The alarm cannot be configured.
VLT® Motion Control Tool MCT 10 has the element numbers listed in the column ID. Use this table with MCT 10 to get information
about specific fault levels.
5.15 Parameter Group 15-** Drive Information
5.15.1 15-0* Operating Data
Parameter 15-00 Operating Hours
Table 761: Parameter 15-00 Operating Hours
Parameter type: Range, 0 - 2147483647 h
Change during operation: False
View for how many hours the drive has run. The value is saved when the drive is turned off.
Parameter 15-01 Running Hours
Table 762: Parameter 15-01 Running Hours
Parameter type: Range, 0 - 2147483647 h
Change during operation: False
View how many hours the motor has run. Reset the counter in parameter 15-07 Reset Running Hours Counter. The value is saved
when the drive is turned off.
Parameter 15-02 kWh Counter
Table 763: Parameter 15-02 kWh Counter
Parameter type: Range, 0 - 2147483647 kWh
Change during operation: False
Register the power consumption of the motor as an average value over 1 hour. Reset the counter in parameter 15-06 Reset kWh
Counter.
AU275636650261en-000101 / 130R0334 | 477Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide