Parameter 4-82 Power Limit Motor Mode
Table 314: Parameter 4-82 Power Limit Motor Mode
4-82 Power Limit Motor Mode
Parameter type: Range, 0.0 - 200.0%
Change during operation: True
Enter the maximum output power when the power limit function is active. Related parameters: parameter 1-20 Motor Power [kW],
parameter 1-21 Motor Power [HP].
Parameter 4-83 Power Limit Generator Mode
Table 315: Parameter 4-83 Power Limit Generator Mode
4-83 Power Limit Generator Mode
Parameter type: Range, 0.0 - 200.0%
Change during operation: True
Enter the maximum generating power when the power limit function is active. Related parameters: parameter 1-20 Motor Power
[kW], parameter 1-21 Motor Power [HP].
5.5.9 4-9* Directional Limits
The directional limits functionality allows to specify different torque and speed limits for different combinations of torque applica-
tion direction and rotation direction. In Illustration 60, quadrants 1–4 show different combinations of rotation direction and torque
application direction, and the parameters that act in different quadrants.
1
2
3 4
par. 4-91,
par. 4-92
par. 4-95
Illustration 60: Example of Directional Limits
A speed limit value cannot exceed the value of parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High
Limit [Hz]. A torque limit value cannot exceed the value of parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit
Generator Mode.