Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X48/10. A high time constant value improves dampening but also increases the time delay through the filter.
Parameter 35-35 Term. X48/10 Temp. Monitor
Table 1295: Parameter 35-35 Term. X48/10 Temp. Monitor
35-35 Term. X48/10 Temp. Monitor
Default value: [0] Disabled
Parameter type: Option
Setup: All setups
Conversion index: -
Data type: Uint8
Change during operation: True
This parameter facilitates the possibility of enabling or disabling the temperature monitor for terminal X48/4. Set the temperature
limits in parameter 35-36 Term. X48/10 Low Temp. Limit and parameter 35-37 Term. X48/10 High Temp. Limit.
Option
Name
Description
[0]*
Disabled
[1]
Enabled
Parameter 35-36 Term. X48/10 Low Temp. Limit
Table 1296: Parameter 35-36 Term. X48/10 Low Temp. Limit
35-36 Term. X48/10 Low Temp. Limit
Default value: Size related
Parameter type: Range, N/A
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10.
Parameter 35-37 Term. X48/10 High Temp. Limit
Table 1297: Parameter 35-37 Term. X48/10 High Temp. Limit
35-37 Term. X48/10 High Temp. Limit
Default value: Size related
Parameter type: Range, N/A
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10.
5.28.5 35-4* Analog Input X48/2
Parameter 35-42 Term. X48/2 Low Current
Table 1298: Parameter 35-42 Term. X48/2 Low Current
35-42 Term. X48/2 Low Current
Default value: 4 mA
Parameter type: Range, 0 - 20 mA
Setup: All setups
Conversion index: -3
Data type: Int16
Change during operation: True
Enter the current (mA) that corresponds to the low reference value set in parameter 35-44 Term. X48/2 Low Ref./Feedb. Value. The
value must be more than 2 mA to activate the live zero timeout function in parameter 6-01 Live Zero Timeout Function.
Parameter 35-43 Term. X48/2 High Current
Table 1299: Parameter 35-43 Term. X48/2 High Current
35-43 Term. X48/2 High Current
Default value: 20 mA
Parameter type: Range, 0 - 20 mA
Setup: All setups
Conversion index: -3
Data type: Int16
Change during operation: True
AU275636650261en-000101 / 130R0334 | 635Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals