Parameter 4-75 Touch Timeout
Table 311: Parameter 4-75 Touch Timeout
Parameter type: Range, 0.1 - 6000.0 s
Change during operation: True
N O T I C E
This parameter is only available with software version 48.XX.
Enter the timeout for the touch probe positioning. If the drive does not detect the touch probe sensor before the timeout when the
touch probe positioning is active, the drive trips with alarm 216, Touch Timeout. The value 6000 equals Off.
5.5.8 4-8* Power Limit
N O T I C E
This parameter group is only available in FC 302.
Parameter 4-80 Power Limit Func. Motor Mode
Table 312: Parameter 4-80 Power Limit Func. Motor Mode
4-80 Power Limit Func. Motor Mode
Default value: [0] Disabled
Change during operation: True
Select whether the power limit function is enabled. Define the power limit motor mode in parameter 4-82 Power Limit Motor Mode.
Activation via a digital input or a fieldbus.
Parameter 4-81 Power Limit Func. Generator Mode
Table 313: Parameter 4-81 Power Limit Func. Generator Mode
4-81 Power Limit Func. Generator Mode
Default value: [0] Disabled
Change during operation: True
Select whether the power limit function is enabled in generating mode. Define the power limit motor mode in parameter 4-83 Power
Limit Generator Mode.
Activation via a digital input or a fieldbus.