5.12.8 12-6* Ethernet POWERLINK
Parameter 12-60 Node ID
Table 646: Parameter 12-60 Node ID
Parameter type: Range, 1 - 239
Change during operation: True
Enter the node ID in this parameter or alternatively in the hardware switch. To adjust the node ID in this parameter, set the hard-
ware switch to 0 or to 255 (all switches set to [ON] or to [OFF]). Otherwise, this parameter shows the actual setting of the switch. The
settings of this parameter take effect at the next power-up cycle.
Table 647: Parameter 12-62 SDO Timeout
Parameter type: Range, 0 - 2000000000
Change during operation: True
This parameter is the SDO Timeout in ms. The value of this parameter is read during communication initialization into Object 1300h.
Parameter 12-63 Basic Ethernet Timeout
Table 648: Parameter 12-63 Basic Ethernet Timeout
12-63 Basic Ethernet Timeout
Parameter type: Range, 0 - 2000000.000 ms
Change during operation: True
This parameter is the basic Ethernet timeout in ms. This parameter is mapped to Object 1F99h. If the POWERLINK interface does not
receive a SoC frame within the specified time, the interface shifts to standard Ethernet mode. This feature is available from version
2.00 of the POWERLINK interface.