Parameter 17-10 Signal Type
Table 915: Parameter 17-10 Signal Type
Default value: [1] RS422 (5V TTL)
Change during operation: False
Select this parameter if 1 or 2 encoders are connected to MCB 102.
Parameter 17-11 Resolution (PPR)
Table 916: Parameter 17-11 Resolution (PPR)
Parameter type: Range, 10 - 16384
Change during operation: False
Enter the number of pulses or periods per revolution (the incremental track).
5.17.3 17-2* Abs. Enc. Interface
Parameters in this group configure the absolute interface of the VLT® Encoder Input MCB 102. Both the incremental and absolute
interfaces are active at the same time.
Parameter 17-20 Protocol Selection
Table 917: Parameter 17-20 Protocol Selection
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Select [0] None if the feedback sensor is an incremental encoder only.
Select [1] HIPERFACE if the encoder is absolute only.
Select 0 pulse as "absolute" track when using incremental encoder with 0 pulse.
AU275636650261en-000101 / 130R0334518 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide