for a time period defined in parameter 6-00 Live Zero Timeout Time, then the function set in parameter 6-01 Live Zero Timeout Function
is activated. If several timeouts occur simultaneously, the drive prioritizes the timeout functions as follows:
Parameter 6-01 Live Zero Timeout Function
Parameter 8-04 Control Word Timeout Function
Frozen at the present value.
Overruled to maximum speed.
Overruled to stop with subsequent trip.
Parameter 6-02 Emergency Mode Live Zero Timeout Function
Table 399: Parameter 6-02 Emergency Mode Live Zero Timeout Function
6-02 Emergency Mode Live Zero Timeout Function
Change during operation: True
Select the timeout function when emergency mode is active. The function set in this parameter is activated if the input signal on
analog inputs is below 50% of the low value for a period defined in parameter 6-00 Live Zero Timeout Time.
Frozen at the present value.
Overruled to maximum speed.
5.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).