5.9.2 8-1* Ctrl. Word Settings
Parameter 8-10 Control Word Profile
Table 503: Parameter 8-10 Control Word Profile
8-10 Control Word Profile
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the
fieldbus installed in slot A are visible in the LCP display. For guidelines in selection of [0] FC profile and [1] PROFIdrive profile, refer to
the product-specific design guide. For more guidelines in the selection of [1] PROFIdrive profile, refer to the Installation Guide for the
installed fieldbus.
Option
Name
Description
[0]
FC profile
[1]
PROFIdrive profile
[3]
FC motion profile
N O T I C E
This option is only available with software version 48.XX.
Assigns motion-specific functions to various control and status word bits. This option is available
when [9] Positioning or [10] Synchronization is selected in parameter 1-00 Configuration Mode.
[5]
ODVA
[7]
CANopen DSP 402
[8]
MCO
Parameter 8-13 Configurable Status Word STW
Table 504: Parameter 8-13 Configurable Status Word STW
8-13 Configurable Status Word STW
Default value: Size related
Parameter type: Option, Array [16]
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the
fieldbus installed in slot A are visible in the LCP display. For more guidelines in the selection of [1] PROFIdrive profile, refer to the
Installation Guide for the installed fieldbus.
Option
Name
Description
[0]
No function
The input is always low.
[1]
Profile default
Dependent on the profile set in parameter 8-10 Control Profile.
[2]
Alarm 68 Only
The input goes high whenever Alarm 68 Safe Stop Activated is active and goes low
whenever Alarm 68 Safe Stop Activated is not activated.
[3]
Trip excl Alarm 68
AU275636650261en-000101 / 130R0334 | 275Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals