Parameter 4-38 Tracking Error Ramping Timeout
Table 284: Parameter 4-38 Tracking Error Ramping Timeout
4-38 Tracking Error Ramping Timeout
Default value: 1 s
Parameter type: Range, 0 - 60 s
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
Enter the timeout period during which an error greater than the value set in parameter 4-37 Tracking Error Ramping while ramping is
allowed.
Parameter 4-39 Tracking Error After Ramping Timeout
Table 285: Parameter 4-39 Tracking Error After Ramping Timeout
4-39 Tracking Error After Ramping Timeout
Default value: 5 s
Parameter type: Range, 0 - 60 s
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
Enter the timeout period after ramping where parameter 4-37 Tracking Error Ramping and parameter 4-38 Tracking Error Ramping
Timeout are still active.
5.5.4 4-4* Speed Monitor
Parameter 4-43 Motor Speed Monitor Function
Table 286: Parameter 4-43 Motor Speed Monitor Function
4-43 Motor Speed Monitor Function
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
N O T I C E
This parameter is only available in the flux control principle.
Select how the drive reacts when the motor speed monitor-function detects overspeed or wrong rotation direction. When the mo-
tor speed monitor is active, the drive detects an error if the following conditions are true for a time period specified in parameter
4-45 Motor Speed Monitor Timeout:
The actual speed differs from the reference speed in parameter 16-48 Speed Ref. After Ramp [RPM].
The difference between the speeds exceeds the value in parameter 4-44 Motor Speed Monitor Max.
In speed closed loop, the actual speed is the feedback from the encoder measured during the time defined in parameter 7-06 Speed
PID Lowpass Filter Time. In open loop, the actual speed is the estimated motor speed.
Speed
nRef
-nRef
0rpm
Time
e30be199.11
Illustration 58: Speed Reference and Maximum Allowed Speed Difference
Solid
line
Parameter 16-48 Speed Ref. After Ramp [RPM]
AU275636650261en-000101 / 130R0334162 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals