Parameter 36-53 Terminal X49/9 Max. Scale
Table 1339: Parameter 36-53 Terminal X49/9 Max. Scale
36-53 Terminal X49/9 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Scale the maximum output of terminal X49/9. For example, the scaling is done for the following reasons:
To provide an output value lower than the maximum possible value.
To provide the full signal range using output values lower than a certain limit.
To know more about how this parameter works, see parameter 6-52 Terminal 42 Output Max Scale. Example:
Parameter 36-04 Terminal X49/9 Mode = [0] Voltage 0–10 V
Parameter 36-50 Terminal X49/9 Analogue Output = [100] Output Frequency.
Parameter 4-19 Max Output Frequency = 200 Hz.
Example case 1: 5 V maximum output is required when the output frequency is 200 Hz. Parameter 36-53 Terminal X49/9 Max. Scale x
100% = 200%. Example case 2: 10 V maximum output is required when the output frequency is 150 Hz (75% of the maximum out-
put frequency). Parameter 36-53 Terminal X49/9 Max. Scale = 75%.
Parameter 36-54 Terminal X49/9 Bus Ctrl
Table 1340: Parameter 36-54 Terminal X49/9 Bus Ctrl
36-54 Terminal X49/9 Bus Ctrl
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: 0
Data type: N2
Change during operation: True
This parameter contains the output level of terminal X49/9 if the terminal is controlled by bus.
Parameter 36-55 Terminal X49/9 Timeout Preset
Table 1341: Parameter 36-55 Terminal X49/9 Timeout Preset
36-55 Terminal X49/9 Timeout Preset
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: 1 setup
Conversion index: 0
Data type: Uint16
Change during operation: True
The drive sends the value of this parameter to the output terminal when the terminal is controlled by a fieldbus and a timeout is
detected.
5.29.7 36-6* Output X49/11
Use the parameters in this group to configure the mode of inputs and outputs of VLT® Programmable I/O MCB 115.
N O T I C E
The following parameter is only available in FC 302:
Parameter 36-61 Terminal X49/11 Digital Output.
Parameter 36-60 Terminal X49/11 Analogue Output
Table 1342: Parameter 36-60 Terminal X49/11 Analogue Output
36-60 Terminal X49/11 Analogue Output
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
AU275636650261en-000101 / 130R0334 | 655Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals