Parameter 7-46 Process PID Feed Fwd Normal/Inv. Ctrl.
Table 477: Parameter 7-46 Process PID Feed Fwd Normal/Inv. Ctrl.
7-46 Process PID Feed Fwd Normal/Inv. Ctrl.
Default value: [0] Normal
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Normal
Select [0] Normal to set the feed-forward factor to treat the FF resource as a positive value.
[1]
Inverse
Select [1] Inverse to treat the feed-forward resource as a negative value.
Parameter 7-48 PCD Feed Forward
Table 478: Parameter 7-48 PCD Feed Forward
7-48 PCD Feed Forward
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
This parameter contains the value of parameter 7-45 Process PID Feed Fwd Resource, [32] Bus PCD.
Parameter 7-49 Process PID Output Normal/Inv. Ctrl.
Table 479: Parameter 7-49 Process PID Output Normal/Inv. Ctrl.
7-49 Process PID Output Normal/Inv. Ctrl.
Default value: [0] Normal
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Normal
Select [0] Normal to use the resulting output from the process PID controller as is.
[1]
Inverse
Select [1] Inverse to invert the resulting output from the process PID controller. This operation is performed
after the feed-forward factor is applied.
5.8.8 7-5* Ext. Process PID Ctrl.
This parameter group is only used if parameter 1-00 Configuration Mode is set to [7] Extended PID speed CL or [8] Extended PID Speed
OL.
Parameter 7-50 Process PID Extended PID
Table 480: Parameter 7-50 Process PID Extended PID
7-50 Process PID Extended PID
Default value: [1] Enabled
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]
Disabled
Disable the extended parts of the process PID controller.
[1]*
Enabled
Enable the extended parts of the PID controller.
AU275636650261en-000101 / 130R0334266 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals