Parameter 7-44 Process PID Gain Scale at Max. Ref.
Table 475: Parameter 7-44 Process PID Gain Scale at Max. Ref.
7-44 Process PID Gain Scale at Max. Ref.
Parameter type: Range, 0 - 100%
Change during operation: True
Enter a scaling percentage to apply to the process PID output when operating at the maximum reference. The scaling percentage is
adjusted linearly between the scale at minimum reference (parameter 7-43 Process PID Gain Scale at Min. Ref.) and the scale at maxi-
mum reference (parameter 7-44 Process PID Gain Scale at Max. Ref.).
Parameter 7-45 Process PID Feed Fwd Resource
Table 476: Parameter 7-45 Process PID Feed Fwd Resource
7-45 Process PID Feed Fwd Resource
Default value: [0] No function
Change during operation: True
Select which drive input should be used as the feed-forward factor. The factor is added to the
output of the PID controller. This increases dynamic performance.
N O T I C E
This option is only available in FC 302.
N O T I C E
This option is only available in FC 302.
Selects a fieldbus reference configured by parameter 8-02 Control Word Source. Change parame-
ter 8-42 PCD Write Configuration for the bus used to make the feed forward available in parame-
ter 7-48 PCD Feed Forward. Use index 1 for feed forward [748] (and index 2 for reference [1682]).
AU275636650261en-000101 / 130R0334 | 265Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide