Parameter 7-51 Process PID Feed Fwd Gain
Table 481: Parameter 7-51 Process PID Feed Fwd Gain
7-51 Process PID Feed Fwd Gain
Default value: 1
Parameter type: Range, 0 - 100
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
The feed forward is used to obtain the required level based on a well-known signal available. The PID controller then only takes care
of the smaller part of the control, necessary because of unknown characters. The standard feed-forward factor in parameter 7-38
Process PID Feed Forward Factor is always related to the reference, whereas parameter 7-51 Process PID Feed Fwd Gain has more op-
tions. In winder applications, the feed-forward factor is typically the line speed of the system.
Parameter 7-52 Process PID Feed Fwd Ramp Up
Table 482: Parameter 7-52 Process PID Feed Fwd Ramp Up
7-52 Process PID Feed Fwd Ramp Up
Default value: 0.01 s
Parameter type: Range, 0.01 - 10 s
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: True
Controls the dynamics of the feed-forward signal when ramping up.
Parameter 7-53 Process PID Feed Fwd Ramp Down
Table 483: Parameter 7-53 Process PID Feed Fwd Ramp Down
7-53 Process PID Feed Fwd Ramp Down
Default value: 0.01 s
Parameter type: Range, 0.01 - 10 s
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: True
Controls the dynamics of the feed-forward signal when ramping down.
Parameter 7-56 Process PID Ref. Filter Time
Table 484: Parameter 7-56 Process PID Ref. Filter Time
7-56 Process PID Ref. Filter Time
Default value: 0.001 s
Parameter type: Range, 0.001 - 1 s
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: True
Set a time constant for the reference first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/feedback signals. However, severe filtering can be detrimental to dynamic performance.
Parameter 7-57 Process PID Fb. Filter Time
Table 485: Parameter 7-57 Process PID Fb. Filter Time
7-57 Process PID Fb. Filter Time
Default value: 0.001 s
Parameter type: Range, 0.001 - 1 s
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: True
Set a time constant for the feedback first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/ feedback signals. However, severe filtering can be detrimental to dynamic performance.
AU275636650261en-000101 / 130R0334 | 267Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals