Enter the increment size required for increase/decrease as a percentage of the synchronous motor speed, n
s
. If increase/decrease is
activated, the resulting reference is increased or decreased by the value set in this parameter.
Parameter 3-91 Ramp Time
Table 257: Parameter 3-91 Ramp Time
3-91 Ramp Time
Default value: 0 s
Parameter type: Range, 0 - 3600 s
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: True
Enter the ramp time, that is the time for adjustment of the reference 0–100% of the specified digital potentiometer function (in-
crease, decrease, or clear). If increase/decrease is activated for longer than the ramp delay period specified in parameter 3-95 Ramp
Delay, the actual reference is ramped up/down according to this ramp time. The ramp time is defined as the time used to adjust the
reference by the step size specified in parameter 3-90 Step Size.
Parameter 3-92 Power Restore
Table 258: Parameter 3-92 Power Restore
3-92 Power Restore
Default value: [0] Off
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Off
Resets the digital potentiometer reference to 0% after power-up.
[1]
On
Restores the most recent digital potentiometer reference at power-up.
Parameter 3-93 Maximum Limit
Table 259: Parameter 3-93 Maximum Limit
3-93 Maximum Limit
Default value: 100%
Parameter type: Range, -200 - 200%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Set the maximum allowed value for the resulting reference. This is recommended if the digital potentiometer is used for fine-tuning
of the resulting reference.
Parameter 3-94 Minimum Limit
Table 260: Parameter 3-94 Minimum Limit
3-94 Minimum Limit
Default value: 100%
Parameter type: Range, -200 - 200%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Set the minimum allowed value for the resulting reference. This is recommended if the digital potentiometer is used for fine-tuning
of the resulting reference.
Parameter 3-95 Ramp Delay
Table 261: Parameter 3-95 Ramp Delay
3-95 Ramp Delay
Default value: Size related
Parameter type: Range, 0 - 0
Setup: All setups
Conversion index: -3
Data type: TimeDiff w/o DateIdent.
Change during operation: True
AU275636650261en-000101 / 130R0334 | 153Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals