Option
Name
Description
[137]
Speed 4–20mA
Taken from parameter 3-03 Maximum Reference. 20 mA = value in parameter 3-03 Maximum Refer-
ence.
[138]
Torque 4–20mA
Torque reference related to 160% torque.
[139]
Bus ctrl.
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[140]
Bus ctrl. 4–20mA
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[141]
Bus ctrl t.o.
Parameter 4-54 Warning Reference Low defines the behavior of the analog output in case of field-
bus timeout.
[142]
Bus ctrl 4-20mA
t.o.
Parameter 4-54 Warning Reference Low defines the behavior of the analog output in case of field-
bus timeout.
[147]
Main act val
[148]
Main act val
4-20mA
[149]
Torque % lim
4-20mA
Analog output at 0 torque is 12 mA. Motoring torque increases the output current to maximum
torque limit 20 mA (set in parameter 4-16 Torque Limit Motor Mode). Generating torque decreases
the output to torque limit in generator mode (set in parameter 4-17 Torque Limit Generator Mode)
Example: Parameter 4-16 Torque Limit Motor Mode = 200% and parameter 4-17 Torque Limit Genera-
tor Mode = 200%. 20 mA = 200% motoring and 4 mA = 200% generating.
[150]
Max Out Fr
4-20mA
0 Hz = 0 mA, parameter 4-19 Max Output Frequency = 20 mA.
[158]
Motor Volt.
[159]
Motor Volt.
4-20mA
Parameter 6-71 Terminal X45/1 Min. Scale
Table 437: Parameter 6-71 Terminal X45/1 Min. Scale
6-71 Terminal X45/1 Min. Scale
Default value: 0%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Scale the minimum output of the selected analog signal at terminal X45/1 as a percentage of the maximum signal value. For exam-
ple, if 0 mA (or 0 Hz) is required at 25% of the maximum output value, then program 25%. Scaling values up to 100% can never
exceed the corresponding setting in parameter 6-72 Terminal X45/1 Max. Scale.
Parameter 6-72 Terminal X45/1 Max. Scale
Table 438: Parameter 6-72 Terminal X45/1 Max. Scale
6-72 Terminal X45/1 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Scale the maximum output of the selected analog signal at terminal X45/1. Set the value to the maximum value of the current signal
output. Scale the output to give a current lower than 20 mA at full scale, or 20 mA at an output below 100% of the maximum signal
value. If 20 mA is the required output current at a value between 0–100% of the full-scale output, program the percentage value in
AU275636650261en-000101 / 130R0334248 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals