Parameter 0-32 Custom Readout Max Value.
Parameter 4-13 Motor Speed High Limit [RPM].
Parameter 4-14 Motor Speed High Limit [Hz].
Actual speed.
Linear Unit (e.g. speed and flow)
Quadratic Unit (Pressure)
P 0-32
Min value
P 0-31
Linear
units only
Motor Speed
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
Illustration 28: Custom Readout
The relation depends on the type of unit selected in parameter 0-30 Custom Readout Unit.
Table 20: Speed Relations for Different Unit Types
Parameter 0-30 Unit for User-defined Readout
Table 21: Parameter 0-30 Unit for User-defined Readout
0-30 Unit for User-defined Readout
Change during operation: True
It is possible to program a value to be shown in the display of the LCP. The value has a linear, squared, or cubed relation to speed.
This relation depends on the unit type selected. The actual calculated value can be read in parameter 16-09 Custom Readout, and/or
shown in the display by selecting [16-09] Custom Readout in parameter 0-20 Display Line 1.1 Small to parameter 0-24 Display Line 3
Large.