Parameter 16-18 Motor Thermal
Table 839: Parameter 16-18 Motor Thermal
Parameter type: Range, 0 - 100%
Change during operation: False
View the calculated thermal load on the motor. The cutout limit is 100%. The basis for calculation is the ETR function selected in
parameter 1-90 Motor Thermal Protection.
Parameter 16-19 Thermistor Sensor Temperature
Table 840: Parameter 16-19 Thermistor Sensor Temperature
16-19 Thermistor Sensor Temperature
Parameter type: Range, 0 - 0 °C
Change during operation: False
Returning the actual temperature on KTY sensor built into the motor. See parameter group 1-9* Motor Temperature.
Parameter 16-20 Motor Angle
Table 841: Parameter 16-20 Motor Angle
Parameter type: Range, 0 - 65535
Change during operation: True
View the current encoder/resolver angle offset relative to the index position. The value range of 0–65535 corresponds to 0–2xpi
(radian).
Parameter 16-21 Torque [%] High Res.
Table 842: Parameter 16-21 Torque [%] High Res.
16-21 Torque [%] High Res.
Parameter type: Range, -200 - 200%
Change during operation: False
The value shown is the torque in percent of nominal torque, with sign and 0.1% resolution, applied to the motor shaft.
Parameter 16-22 Torque [%]
Table 843: Parameter 16-22 Torque [%]
Parameter type: Range, -200 - 200%
Change during operation: False
The value shown is the torque in percent of nominal torque, with sign, applied to the motor shaft.
Parameter 16-23 Motor Shaft Power [kW]
Table 844: Parameter 16-23 Motor Shaft Power [kW]
16-23 Motor Shaft Power [kW]
Parameter type: Range, 0 - 10000 kW
Change during operation: True
AU275636650261en-000101 / 130R0334500 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide