EasyManuals Logo
Home>Ecolab>Water Pump>EcoAdd

Ecolab EcoAdd User Manual

Ecolab EcoAdd
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
Type 03003S:
Metering
mode Display
Metering
output
100 %
(V)
Max. stroke
frequency
at 100%
(¦)
Stroke
volume
(V
h
)
Suction
stroke
Duration
(S
t
)
min. metering
stroke
duration
(P
t
)
Standard
30 l/h 155 / min
3,4 ml
190 ms
197 ms
Medium 25 l/h 141 / min 228 ms
Low 20 l/h 111 / min 342 ms
Variable
15 - 30 l/h 104 - 155 / min 380 - 190 ms
Type 05010M:
Metering
mode Display
Metering
output
100 %
(V)
Max. stroke
frequency
at 100%
(¦)
Stroke
volume
(V
h
)
Suction
stroke
Duration
(S
t
)
min. metering
stroke
duration
(P
t
)
Standard 54 l/h 159 / min
5,8 ml
185 ms
192 ms
Medium
45 l/h 145 / min 222 ms
Low 36 l/h 114 / min 333 ms
Variable 27 - 54 l/h 107 - 159 / min 370 - 185 ms
Type 12003M:
Metering
mode Display
Metering
output
100 %
(V)
Max. stroke
frequency
at 100%
(¦)
Stroke
volume
(V
h
)
Suction
stroke
Duration
(S
t
)
min. metering
stroke
duration
(P
t
)
Standard 120 l/h 148 / min
13.5 ml
200 ms
205 ms
Medium 100 l/h 135 / min 240 ms
Low
80 l/h 106 / min 360 ms
Variable 60 - 120 l/h 99 - 148 / min 400 - 200 ms
Operation
145 Rev. 2-05.2018

Table of Contents

Other manuals for Ecolab EcoAdd

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ecolab EcoAdd and is the answer not in the manual?

Ecolab EcoAdd Specifications

General IconGeneral
BrandEcolab
ModelEcoAdd
CategoryWater Pump
LanguageEnglish

Related product manuals