13.5 Electrical data
Name
Type
00510X
Type
01
110S
Type
03003M
Type
05010M
Type
12003M
Supply voltage [V / Hz] 100 - 240 ±10% / 50/60
Motor power [W] 30 50
IP Code IP65
Appliance class II
Inputs:
Level, external release, batch max. 24 V DC / 6 mA
Pulse, standard signal (0/4-20 mA) max. 25 mA (approx. 50 Ohm)
Minimum pulse duration (On/Off) 15 mS
Outputs:
Alarm (relay contact) 230 V, AC/DC, 3 A
Stroke signal (transistor) max. 24 V, DC, 200 mA
External power supply 5 V, max. 100 mA
Permissible cables:
Permissible external cable diameters for connecting the inputs/outputs:
AD Ø = 5.1-5.7 mm. LIYY 4 x 0.5; LIYY 5 x 0.34; L
YCY 2 x 0.34
Permissible cables: Ölflex 4 x 0.5
The IP65 is applicable only when the specified cable is being used.
13.6 Materials
n Enclosure:
PPO (Noryl)
n Metering head:
PP
, optionally PVDF, stainless steel 1.4571
n Diaphragm:
PTFE - EPDM composite diaphragm
n Seals:
FKM or EPDM, either PTFE or FFPM (Kalrez)
n Valve balls:
Ceramic, either PTFE or stainless steel 1.4401
n Valve springs:
Hastelloy C4
n Colour:
Blue RAL 5007
Special versions are available on request.
Technical data
189 Rev. 2-05.2018

Table of Contents

Other manuals for Ecolab EcoAdd

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ecolab EcoAdd and is the answer not in the manual?

Ecolab EcoAdd Specifications

General IconGeneral
BrandEcolab
ModelEcoAdd
CategoryWater Pump
LanguageEnglish

Related product manuals