7-2 SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
350 IEC 1588 PRECISION TIME PROTOCOL (PTP) CHAPTER 7: 350 TIME PROTOCOLS
350 Real Time Clock
PATH: SETPOINTS > S1 RELAY SETUP > CLOCK
PTP FUNCTION
Range: Enabled, Disabled
Default: Disabled
When “Disabled” is selected for this setting, PTP is disabled on the port. The relay does
not generate, or listen to, PTP messages on the port.
PTP STRICT POWER PROFILE
Range: Enabled, Disabled
Default: Disabled
Power profile (IEEE Std C37.238 2011) requires that the relay selects as a grandmaster:
only power profile compliant clocks
that the delivered time has a worst-case error of ±1 μs
and, that the peer delay mechanism be implemented.
With the Strict Power Profile setting set to “Enabled”, the relay selects as the master only
clocks displaying the IEEE_C37_238 identification codes. It uses a port only when the
peer delay mechanism is operational. With the
Strict Power Profile setting set to
“Disabled”, the relay uses clocks without the power profile identification when no power
profile clocks are present, and uses ports even if the peer delay mechanism is non-
operational. This setting applies to all of the relay’s PTP-capable ports.
PTP DOMAIN NUMBER
Range: 0 to 255
Default: 0
The setting is set to the domain number of the grandmaster-capable clock(s) to which
they can be synchronized. A network can support multiple time distribution domains,
each distinguished with a unique domain number. More commonly, there is a single
domain using the default domain number zero. The setting applies to all of the relay’s
PTP-capable ports.
PTP VLAN PRIORITY
Range: 0 to 7
Default: 4
The setting selects the value of the priority field in the 802.1Q VLAN tag in request
messages issued by the relay’s peer delay mechanism. In compliance with PP (Power
Profile) the default VLAN priority is 4, but it is recommended that in accordance with PTP
it be set to 7.
Depending on the characteristics of the device to which the relay is directly linked, VLAN
Priority may have no effect.
The setting applies to all of the relay’s PTP-capable ports.
PTP VLAN ID
Range: 0 to 4095
Default: 0
The setting selects the value of the ID field in the 802.1Q VLAN tag in request messages
issued by the relay’s peer delay mechanism. It is provided in compliance with PP (Power
Profile).
As these messages have a destination address that indicates they are not to be bridged,
their VLAN ID serves no function, and so may be left at its default value. Depending on
the characteristics of the device to which the relay is directly linked, VLAN ID may have
no effect.
The setting applies to all of the relay’s PTP-capable ports