3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A–59
PIXIT for Server model
* IEC 61850-6:2009 clause 9.5.6 states that if only a subrange of the enumeration value set
is supported, this shall be indicated within an ICD file by an enumeration type, where the
unsupported values are missing
ID Ed Description Value / Clarification
Sr1 1,2 Which analogue value (MX) quality bits
are supported (can be set by server)
Validity:
Y
N
N
N
N
N
N
N
N
N
N
N
Source:
Y
N
N
N
Good,
Invalid,
Reserved,
Questionable
Details:
Overflow
OutofRange
BadReference
Oscillatory
Failure
OldData
Inconsistent
Inaccurate
Process
Substituted
Test
OperatorBlocked
Sr2 1,2 Which status value (ST) quality bits are
supported (can be set by server)
Validity:
Y
N
N
N
N
N
N
N
N
N
Source:
Y
N
N
N
Good,
Invalid,
Reserved,
Questionable
Details:
BadReference
Oscillatory
Failure
OldData
Inconsistent
Inaccurate
Process
Substituted
Test
OperatorBlocked
Sr3 - What is the maximum number of data
object references in one GetDataValues
request
Deprecated
Sr4 - What is the maximum number of data
object references in one SetDataValues
request
Deprecated
Sr5 1 Which Mode values are supported* On
[On-]Blocked
Test
Test/Blocked
Off
Y
N
N
N
N

Table of Contents