EasyManuals Logo

GE 350 User Manual

GE 350
786 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #755 background imageLoading...
Page #755 background image
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE A–37
3.2 Common data class specifications for measurand information
3.2.1 Measured Value (MV)
MV_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
measured attributes
instMag FloatAnalogueValue MX ------ O
f FLOAT32 GC_1
mag FloatAnalogueValue MX dchg M
f FLOAT32 GC_1
range ENUMERATED(Byte) MX dchg O
q BVstring13 MX qchg M
t Utctime MX M
configuration, description and extension
units Unit CF O
SIUnit ENUMERATED(Byte) M
Multiplier ENUMERATED(Byte) O
db INT32U CF O
zeroDb INT32U CF O
rangeC RangeConfig CF O
hhLim FloatAnalogueValue
f FLOAT32 GC_1
hlim FloatAnalogueValue
f FLOAT32 GC_1
lLim FloatAnalogueValue
f FLOAT32 GC_1
llLim FloatAnalogueValue
f FLOAT32 GC_1
min FloatAnalogueValue
f FLOAT32 GC_1
max FloatAnalogueValue
f FLOAT32 GC_1
limDb INT32U
d Vstring255 DC O

Table of Contents