A–52 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PICS
2 ASCI basic conformance statement
The basic conformance statement is defined in Table A.1.
Table A.1: Basic conformance statement
Client/
Subscriber
Server/
Publisher
Value/
Comments
Client-Server roles
B11 Server side (of TWO-PARTY-
APPLICATION-ASSOCIATION)
- Y
B12 Client side of (TWO-PARTY-
APPLICATION-ASSOCIATION)
-
SCSMs supported
B21 SCSM: IEC 6185-8-1 used Y
B22 SCSM: IEC 6185-9-1 used Deprecated
B23 SCSM: IEC 6185-9-2 used
B24 SCSM: other
Generic substation event model (GSE)
B31 Publisher side - Y
B32 Subscriber side Y -
Transmission of sampled value model (SVC)
B41 Publisher side -
B42 Subscriber side -
- = not applicable
Y = supported