5-52 L60 Line Phase Comparison System GE Multilin
5.2 PRODUCT SETUP 5 SETTINGS
5
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
5.2.15 USER-DEFINABLE DISPLAYS
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-DEFINABLE DISPLAYS
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the USER DISPLAYS menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus facili-
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
KEYPAD: Use the MENU key to select the USER DISPLAYS menu item to access the first user-definable display (note
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the
PRODUCT SETUP ÖØ DISPLAY PROPER-
TIES ÖØ DEFAULT MESSAGE TIMEOUT setting.
USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
gate the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The
INVOKE AND SCROLL input and the DOWN key operate concurrently.
When the default timer expires (set by the
DEFAULT MESSAGE TIMEOUT setting), the relay will start to cycle through the
user displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user dis-
play, not at the first user-defined display. The
INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.
USER-DEFINABLE
DISPLAYS
INVOKE AND SCROLL:
Off
Range: FlexLogic™ operand
MESSAGE
USER DISPLAY 1
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 2
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 16
Range: up to 20 alphanumeric characters

Table of Contents

Other manuals for GE UR series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE UR series and is the answer not in the manual?

GE UR series Specifications

General IconGeneral
TypeProtective Relay
SeriesUR (Universal Relay)
Frequency Range50/60 Hz
ManufacturerGE (General Electric)
Communication ProtocolsIEC 61850, DNP3, Modbus
MountingPanel
DisplayLCD display
Operating Temperature-40°C to +70°C
Protection FunctionsOvercurrent, differential, distance, frequency, voltage

Related product manuals