GE Multilin L60 Line Phase Comparison System D-9
APPENDIX D D.1 PROTOCOL
D
Maximum range of values k: 1 to 32767 (2
15
1) APDUs, accuracy 1 APDU
Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU
Recommendation: w should not exceed two-thirds of k.
Portnumber:
RFC 2200 suite:
RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in the Internet
as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual standards used in the Inter-
net. The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen
by the user of this standard.
4 Ethernet 802.3
Serial X.21 interface
Other selection(s) from RFC 2200 (list below if selected)
D.1.2 POINT LIST
The IEC 60870-5-104 data points are configured through the
SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP /
IEC104 POINT LISTS menu. Refer to the Communications section of Chapter 5 for additional details.
PARAMETER VALUE REMARKS
Portnumber 2404 In all cases

Table of Contents

Other manuals for GE UR series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE UR series and is the answer not in the manual?

GE UR series Specifications

General IconGeneral
BrandGE
ModelUR series
CategoryRelays
LanguageEnglish

Related product manuals