EasyManua.ls Logo

GE UR series User Manual

GE UR series
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #408 background imageLoading...
Page #408 background image
5-276 L60 Line Phase Comparison System GE Multilin
5.9 TESTING 5 SETTINGS
5
5.9.3 FORCE CONTACT OUTPUTS
PATH: SETTINGS ÖØ TESTING ÖØ FORCE CONTACT OUTPUTS
The relay contact outputs can be pre-programmed to respond to the test mode.
If set to “Disabled”, the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to “Energized”, the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to “De-ener-
gized”, the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to “Freeze”, the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1
For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
“Latched” (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1
should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should
freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational.
The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the
SETTINGS ÖØ
TESTING Ö TEST MODE menu: TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE:PUSHBUTTON 1 ON
Make the following changes to configure the contact inputs and outputs. In the SETTINGS ÖØ TESTING ÖØ FORCE CONTACT
INPUTS and FORCE CONTACT OUTPUTS menus, set:
FORCE Cont Ip 1: “Disabled”, FORCE Cont Ip 2: “Open”, FORCE Cont Ip 3: “Open”, and FORCE Cont Ip 4: “Closed”
FORCE Cont Op 1: “Freeze”, FORCE Cont Op 2: “De-energized”, FORCE Cont Op 3: “Energized”,
and
FORCE Cont Op 4: “Disabled”
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as “Latched”. Write the following FlexLogic™ equation:
Set the user-programmable pushbutton as latching by changing
SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE
PUSHBUTTONS
Ö USER PUSHBUTTON 1 Ö PUSHBUTTON 1 FUNCTION to “Latched”. To enable either pushbutton 1 or remote
input 1 to initiate the Test mode, make the following changes in the
SETTINGS ÖØ TESTING Ö TEST MODE menu:
TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE:VO1
FORCE CONTACT
OUTPUTS
FORCE Cont Op 1
:Disabled
Range: Disabled, Energized, De-energized, Freeze
MESSAGE
FORCE Cont Op 2
:Disabled
Range: Disabled, Energized, De-energized, Freeze
MESSAGE
FORCE Cont Op xx
:Disabled
Range: Disabled, Energized, De-energized, Freeze

Table of Contents

Other manuals for GE UR series

Question and Answer IconNeed help?

Do you have a question about the GE UR series and is the answer not in the manual?

GE UR series Specifications

General IconGeneral
TypeProtective Relay
SeriesUR (Universal Relay)
Frequency Range50/60 Hz
ManufacturerGE (General Electric)
Communication ProtocolsIEC 61850, DNP3, Modbus
MountingPanel
DisplayLCD display
Operating Temperature-40°C to +70°C
Protection FunctionsOvercurrent, differential, distance, frequency, voltage

Summary

1 GETTING STARTED

1.1 IMPORTANT PROCEDURES

Covers essential procedures for relay setup, including cautions and warnings, and inspection checklists.

1.2 UR OVERVIEW

Provides an overview of the Universal Relay (UR) series, its architecture, and key concepts.

1.3 ENERVISTA UR SETUP SOFTWARE

Details the EnerVista UR Setup software, including PC requirements, installation, and configuration.

1.4 UR HARDWARE

Describes the hardware components of the UR series relay, including mounting, wiring, and communication options.

1.5 USING THE RELAY

Covers the operation of the relay, including keypad navigation, menu hierarchy, relay activation, passwords, FlexLogic customization, and commissioning.

2 PRODUCT DESCRIPTION

2.1 INTRODUCTION

Provides an overview of the L60 Line Phase Comparison System, its features, and applications.

2.2 SPECIFICATIONS

Details the technical specifications of the L60 relay, including protection elements, inputs, outputs, and communications.

2.1.2 ORDERING

Provides information on how to order the L60 relay, including available modules and configurations.

2.1.3 REPLACEMENT MODULES

Lists the order codes for replacement modules for the L60 relay.

3 HARDWARE

3.1 DESCRIPTION

Describes the hardware components of the L60 relay, including physical dimensions and module installation.

3.2 WIRING

Provides details on the wiring of the L60 relay, including typical configurations, control power, and module connections.

3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS

Explains the direct input and output features for inter-relay communications, including fiber optic and RS422 interfaces.

3.4 MANAGED ETHERNET SWITCH MODULES

Details the managed Ethernet switch modules supported by UR-series relays, including hardware, LED indicators, and configuration.

4 HUMAN INTERFACES

4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE

Describes the graphical user interface (GUI) of the EnerVista UR Setup software.

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

Covers advanced features of the EnerVista UR Setup software, including settings templates, FlexLogic equation security, and settings file traceability.

4.3 FACEPLATE INTERFACE

Details the relay's faceplate interface, including enhanced and standard panel options, LED indicators, and keypad operations.

5 SETTINGS

5.1 OVERVIEW

Provides an overview of the settings structure, including main menu, elements, and AC sources.

5.2 PRODUCT SETUP

Covers product setup configurations, including security, display properties, clear relay records, and communications.

5.3 SYSTEM SETUP

Details system setup parameters, including current banks, voltage banks, and power system configurations.

5.4 FLEXLOGIC™

Explains the FlexLogic™ programming language, equation editor, timers, FlexElements™, and non-volatile latches.

5.5 GROUPED ELEMENTS

Describes grouped elements, including phase comparison, line pickup, distance, power swing detect, and load encroachment.

5.6 CONTROL ELEMENTS

Covers control elements such as trip bus, setting groups, selector switches, trip outputs, synchrocheck, digital elements, counters, monitoring elements, pilot schemes, autoreclose, and breaker control.

5.7 INPUTS/OUTPUTS

Details the relay's inputs and outputs, including contact inputs/outputs, virtual inputs/outputs, remote devices, and direct I/O.

5.8 TRANSDUCER INPUTS AND OUTPUTS

Describes transducer inputs and outputs, including dcmA and RTD inputs, and dcmA outputs.

5.9 TESTING

Covers the relay's testing capabilities, including test mode, forcing contact inputs, and forcing contact outputs.

6 ACTUAL VALUES

6.1 OVERVIEW

Provides an overview of the actual values section, including menus for status, metering, records, and product information.

6.2 STATUS

Displays the status of contact inputs, virtual inputs, remote inputs, remote double-point status inputs, teleprotection inputs, contact outputs, virtual outputs, autoreclose, remote devices, digital counters, selector switches, Flex States, and Ethernet switch.

6.3 METERING

Details the metering conventions and displays values for various sources, including phase current, ground current, phase voltage, auxiliary voltage, power, and frequency.

6.4 RECORDS

Provides access to stored records, including fault reports, event records, oscillography, data logger, and breaker maintenance.

6.5 PRODUCT INFORMATION

Provides information about the product, including model details and firmware revisions.

7 COMMANDS AND TARGETS

7.1 COMMANDS

Covers relay directives and operations personnel, including virtual inputs, clear records, set date/time, and relay maintenance.

7.2 TARGETS

Displays the status of active targets and provides information on target messages and self-test errors.

8 THEORY OF OPERATION

8.1 OVERVIEW

Provides an overview of phase comparison relaying, including fundamental principles, variations, and excitation methods.

8.2 SINGLE-POLE TRIPPING

Explains single-pole tripping operations, including phase selection and scheme logic.

8.3 FAULT LOCATOR

Details the fault type determination and calculation algorithms used by the L60 relay.

9 APPLICATION OF SETTINGS

9.1 PHASE COMPARISON ELEMENT 87PC

Describes the 87PC phase comparison element, its description, use of settings, and an example.

9.2 DISTANCE BACKUP/SUPERVISION

Covers distance backup and supervision features, including lines with tapped transformers, transformer load currents, LV-side faults, and transformer inrush current.

9.3 POTT SIGNALING SCHEME

Describes the Permissive Overreaching Transfer Trip (POTT) scheme for two-terminal line applications.

9.4 SERIES COMPENSATED LINES

Discusses distance settings for series compensated lines, considering factors like capacitor banks and sub-synchronous oscillations.

9.5 UNDERSTANDING L60 OSCILLOGRAPHY

Explains how to use the L60 oscillography feature for tuning, commissioning, and troubleshooting phase comparison.

APPENDIX A FLEXANALOG PARAMETERS

A.1 PARAMETER LIST

Provides a detailed list of FlexAnalog data items, including addresses, names, units, and descriptions.

APPENDIX B MODBUS COMMUNICATIONS

B.1 OVERVIEW

Provides an overview of Modbus communications, including protocols, physical layer, and data link layer.

B.2 MODBUS FUNCTION CODES

Details the Modbus function codes supported by the relay, including read, write, and execute operations.

B.3 FILE TRANSFERS

Explains how to obtain relay files via Modbus, including COMTRADE, oscillography, and data logger files.

B.4 MEMORY MAPPING

Provides a detailed mapping of the Modbus memory, listing addresses, register names, ranges, and default values.

APPENDIX C IEC 61850 COMMUNICATIONS

C.1 OVERVIEW

Provides an overview of the IEC 61850 standard and its components.

C.2 SERVER DATA ORGANIZATION

Describes the data organization within the L60 for IEC 61850, including logical nodes and data objects.

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

Explains how to configure the L60 for IEC 61850 using the EnerVista UR Setup software.

APPENDIX D DNP PROTOCOL

D.1 PROTOCOL

Details the IEC 60870-5-104 protocol, including system definition, network configuration, physical layer, and link layer.

D.1.2 POINT LIST

Lists the DNP and IEC 60870-5-104 data points and their configuration.

APPENDIX E DNP DEVICE PROFILE DOCUMENT

E.1 DEVICE PROFILE DOCUMENT

Provides the DNP v3.00 device profile, including supported objects, functions, and timeouts.

E.2 DNP POINT LISTS

Lists the DNP binary input points, binary and control relay outputs, and counters.

APPENDIX F MISCELLANEOUS

F.1 CHANGE NOTES

Lists major updates and changes for L60 manual revisions.

F.2 ABBREVIATIONS

Provides a standard abbreviations list for technical terms used in the manual.

F.3 WARRANTY

Details the GE Multilin relay warranty information, including terms and limitations.

Related product manuals