Firmware 11.00 - DMS 8.0 EN - 10/2011 L 277
8400 StateLine C | Reference manual
I/O terminals
Analog terminals
6.2.1.1 Signal adaptation by means of characteristic
This function extension is only available from version 04.00.00!
An individual characteristic according to the illustration below can be parameterised for
the analog input via the subcodes of C00010
to provide different slopes and a dead band.
In this case the input signal corresponds to the X axis and the output signal corresponds to
the Y axis:
[6-4] Characteristic for analog inputs
In the »Engineer«, there is a parameterising dialog for entering the characteristic. This
dialog also displays the set characteristic graphically.
199.99 %
y
max
-y
max
-x
max
x
max
y
min
-y
min
199.99 %
-199.99 %
-199.99 %
Parameter Info Lenze setting
Value Unit
C00010/1 n AIN1: (+y0) = min 0.00 %
C00010/2
o AIN1: (+x0) = Dead band 0.00 %
C00010/3
p AIN1: (-y0) = (-min) 0.00 %
C00010/4
q AIN1: (-x0) = (-Dead band) 0.00 %
C00010/5
r AIN1: (+ymax) 199.99 %
C00010/6
s AIN1: (+xmax) 199.99 %
C00010/7
t AIN1: (-ymax) 199.99 %
C00010/8
u AIN1: (-xmax) 199.99 %
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for Lenze 8400 StateLine C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 StateLine C and is the answer not in the manual?

Lenze 8400 StateLine C Specifications

General IconGeneral
BrandLenze
Model8400 StateLine C
CategoryInverter Drive
LanguageEnglish

Related product manuals