ENGLISH – 27
8.2 LEVEL 1 PROGRAMMING (ON-OFF)
All Level 1 functions are factory-set to “OFF” and can be modied at any time. To check the various functions, refer to “Table 19”.
8.2.1 LEVEL 1 PROGRAMMING PROCEDURE
m
The user has maximum 20 seconds to press the buttons consecutively during the programming procedure. After this time,
the procedure terminates automatically and memorises the changes made up to that time.
To perform Level 1 programming:
1. press and hold the
g
button until LED “L1” starts ashing
2. release the
g
button
3. press the
f
or
h
button to move the ashing LED to the LED associated with the function to be modied
4. press and release the
g
button immediately to change the status of the function:
– short ash = OFF
– long ash = ON
5. wait 20 seconds (maximum time), without pressing any button, to exit the programming mode.
l
To set other functions to “ON” or “OFF”, while the procedure is running, repeat points 3 and 4 during the phase itself.
Table 19
LEVEL 1 FUNCTIONS (ON-OFF)
LED Function Description
L1 Automatic closing
Function ON: after a complete opening manoeuvre there is a pause (equal to the set pause time), after which the control
unit automatically starts a closing manoeuvre.
Function OFF: the system works in “semi-automatic” mode.
L2 Close after photo
Function ON: the behaviour changes depending on whether the “Automatic Closing” function is enabled or not.
When “Automatic closing” is not active: The door always reaches the fully open position (even if Photo is disengaged
beforehand). When Photo disengages, automatic closing is triggered with a 5-second pause.
When “Automatic Closing” is enabled: the opening manoeuvre stops immediately after the photocells have disengaged.
After 5 seconds, the gate will start closing automatically.
The “Close After Photo” function is always disabled in manoeuvres interrupted by a Stop command.
Function OFF: the pause time is that which has been programmed or automatic re-closing will not take place if the
function is disabled.
L3 Always Close
Function ON: in the event of a blackout, even of short duration, if the control unit detects that the automation is open once
the electricity is restored, it automatically starts a closing manoeuvre, preceded by a 5-second pre-ashing sequence.
Function OFF: when the power is restored, the automation maintains its current position.
L4 Stand-by
Function ON: the function allows for reducing consumption as after 1 minute (programmable time) from the end of each
manoeuvre, the control unit switches off the BlueBus transmitters and all the control unit LEDs, with the exception of the
BlueBus LED which ashes (green) more slowly. When the control unit receives a movement command, it restores full
operation. This function is particularly useful in the operating mode with back-up battery.
Function OFF: normal operation.
Warning! The stand-by function has various modes that can be activated through compatible interfaces.
L5 Anti-tamper
Function ON: after the closing of the door, if a tampering attempt is detected, a signal is sent to the app and a new closing
manoeuvre is forced.
Function OFF: normal operation.
L6 Pre-ashing
Function ON: a 3-second (congurable) pause can be added between the switching on of the warning light and the start of
the manoeuvre, to warn the user in advance of a potentially dangerous situation.
Function OFF: the signalling of the warning light coincides with the start of the manoeuvre
L7
Deactivate internal
radio
Function ON: deactivates the receiver of the radio inside the control unit.
Function OFF: normal operation.
Warning. Activate this function if you are using a type OXI / OXIBD external receiver.
L8
Light / heavy door
mode
Function ON: Congures the control unit with the pre-set parameters (force, sensitivity and speed) optimised for managing
a door regarded as “light”.
Function OFF: Congures the control unit with the pre-set parameters (force, sensitivity and speed) optimised for
managing a door regarded as “heavy”.
WARNING: The pre-sets indicated above are modied automatically whenever the parameter setting is modied. When
exiting the programming menu, the user will be asked to perform a new force search action 8 (see Automatic force
search).
With the motor stationary, LEDs “L1 ... L8” are lit or off depending on the status of the respective function; for example: “L1” is lit when the “Automatic
Closing” function is enabled. During the manoeuvre, LEDs “L1 ... L8” ash to signal the force required to move the door at that time.
If “L1” ashes, the force required is low and so forth, until LED “L8” ashes to signal the maximum force.
There is no relation between the force level indicated by the LEDs during the movement (which is an absolute value) and the level indicated by the LEDs
during the force (which is a relative value) programming phase. See “L6” in “Table 20”.