Setting Conditions for Communications with Host by Using Memory Switches Section 6-7
6-7-1 About Communications Conditions
Items Set for
Communications
Conditions
The following settings are made for the communications conditions for com-
munications between the NT31/NT31C and the host.
Port Communications Method/Communications Type Settings
Communications Condition Settings for The Host Link Method
Communications Condition Settings for The NT link (1:1) Method
No further communications conditions need to be set.
Communications Conditions Settings for The NT Link (1:N) Method
Setting The Conditions for Communications with The Memory Link
Method
Setting Item Function Setting Options Page
Comm. A Method Set the communications method used at serial
port A. Depending on the communications
method, further communications condition set-
tings may be necessary.
A system program for OMRON model.
None/Host Link/NT Link (1:1)/
NT Link (1:N) (standard or high-
speed)/Bar-Code Reader
Memory link
161
163
164
189
166
Comm. B Select Set whether serial port B is to be used for RS-
232C or RS-422A communications.
RS-232C/RS-422A 168
Comm. B Method Set the communications method used at serial
port B. Depending on the communications
method, further communications condition set-
tings may be necessary.
A system program for OMRON model.
None/Host Link/NT Link (1:1)/
NT Link (1:N) (standard or high-
speed)
Memory link
161
163
164
166
Setting Item Function Setting
Options
Page
Comm. Speed
(for host link only)
Sets the communications speed
for communications with the host.
9600 bps/
19200 bps
161
Setting Item Function Setting
Options
Page
Unit No.
(for NT link (1:N) only)
Set the unit number of the NT31/
NT31C.
0 to 7 164
Comm. Speed Sets the communications speed
for communications with the host.
Standard or
high-speed
Setting Item Function Setting
Options
Page
Data bits Set the data bits length. 7, 8 bits 166
Stop bits Set the stop bits length. 1, 2 bits
Parity Set the parity. None, even, odd
Comm. Speed Set the communications speed for
communications with the host.
1200, 2400,
4800, 9600,
19200, 38400
bps
Flow control Set the flow control and its
method.
None, RS/CS,
XON/XOFF
Response Set whether the response is car-
ried out for normal process of
communications command or not.
Ye s , No

Table of Contents

Other manuals for Omron NT31

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NT31 and is the answer not in the manual?

Omron NT31 Specifications

General IconGeneral
BrandOmron
ModelNT31
CategoryTouch terminals
LanguageEnglish

Related product manuals