13.23.2 Programming Contact ID
The Contact ID signalling protocol can also be used. However the programming differs from Fast Format,
here you have to select the content types you would like to be sent to the Alarm Receiving Centre. The table
below shows the types you may have.
Content Types
01 Arm All arm events (by area/level & user name)
02 Disarm All disarm events (by area/level & user name)
03 Special Disarm Disarm events initiated by codes 15 to 20 only
04 Arm Fail Attempt to arm the system failed
05 Alarm All alarm events (by partition, level and type) inc. code guess (excludes
tampers and emergency input types)
06 First alarm First to alarm event (for each input) only
07 Alarm Silenced Any alarm/fault silenced (by partition)
08 Confirmed Sequentially confirmed alarm
09 LoTechFault Telecom Line restore (STU/ATE or DigiModem)
10 HiTechFault Low volts, Battery fault/OK, Fuse failure, RS-485 or Device Failure
11 Tech Info System restart, Over current, Logs cleared
12 Manager Info Code changed / deleted
13 Engineer Info Engineer accessing system, and leaving
14 *AccessC Alarm Access Control door forced or left open
15 *AccessC Info Access Control tag at Reader
16 *AccessC Ref Access refused (invalid code)
17 *SL SwitchOn +Switcher input active
18 *SL SwitchOff +Switcher input restored
19 *SL OtherOn +Other input active
20 *SL OtherOff +Other input restored
+ - Signalled ONLY for inputs with ‘Special Logged’
attribute.
21 *Sub-partitions Set Arming events for sub-partitions
22 *Sub-partitions
Unset
Disarming events for sub-partitions
23 *Sub-partitions
Alarm
Alarm event in a sub-partition
24 Input Omitted Input omitted at rearm.
25 Input Restore Restore of type 05
26 Test Call Do not Use
27 Mains fail Mains fail/restore
28 Emergency input Fire, Gas, HU, 2-key HU, Duress Code used
29 Emergency
Restore
Restore of Fire, Gas, HU.
30 Tamper input Tamper, Day alarm, and Trouble input types. Tamper on input, case tamper
and SAB tamper.
31 First Tamper input First to alarm of tamper input.
32 Tamp Input
Restore
Restore of a tamper.
*Not available on the PCX 26/SMS