QSHT 5700 Inverter Safe Torque-off Function
Introduction
QuickStick HT User Manual 265
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
Performance Level (PL) and Safety Integrity Level (SIL)
For safety-related control systems, Performance Level (PL), according to ISO 13849-1, and
SIL levels, according to IEC 61508 and IEC 62061, include a rating of the systems ability to
perform its safety functions. All of the safety-related components of the control system must
be included in both a risk assessment and the determination of the achieved levels.
See the ISO 13849-1, IEC 61508, and IEC 62061 standards for complete information on
requirements for PL and SIL determination.
Average Frequency of a Dangerous Failure
Safety-related functions are classified as operating in a High-demand/continuous mode. The
SIL value for a High-demand/continuous mode safety-related function is directly related to
the probability of a dangerous failure per hour (PFH).
PFH calculation is based on the equations from IEC 61508 and shows worst-case values.
Table 7-1 provides data for a 20-year proof test interval and demonstrates the worst-case
effect of various configuration changes on the data.
IMPORTANT Determination of safety parameters is based on the assump-
tions that the system operates in High-demand mode and that
the safety function is requested at least once every three
months.
Table 7-1: Safety Circuit Relevant Parameters
Attribute
MMI-HT-C2198-D032
Inverter
Hardware Fault Tolerance (HFT)
*
* Hardware fault tolerance is the minimum number of faults that the safety sys-
tem can tolerate without a loss of the safety function as defined by IEC
61508-2.
1
Mode of operation High-demand/continuous
STO function components type
according to IEC 61508-2
Type B
PFH (1e-9/hour) 1.89
MTTFd 195 years
Proof Test Interval
†
† No proof test-related maintenance is required within 20 years mission time.
20 years
Diagnostic Coverage (DC) 90%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation MagneMotion QuickStick HT and is the answer not in the manual?

Rockwell Automation MagneMotion QuickStick HT Specifications

General IconGeneral
BrandRockwell Automation
ModelMagneMotion QuickStick HT
CategoryAccessories
LanguageEnglish

Related product manuals