Maintenance
Troubleshooting
296 MagneMotion
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
QSHT 5700 Inverter Fault Troubleshooting
Table 8-8 provides detailed descriptions and solutions for the QuickStick HT safety faults as
identified through the MMI_path_qs_ht_faults_status tag. See the Host Controller Ether-
Net/IP Communication Protocol User Manual, MMI-UM004, for a complete description of
all faults and their resolution.
In the QuickStick HT motor error descriptions that are provided in Table 8-8, the Motor Sus-
pend Fault field shows when motion on the motor is suspended. Motion cannot resume until
the fault is cleared. Vehicles are not allowed to enter the section of the Path where the motor is
located while the motor is suspended.
Table 8-8: QuickStick HT MMI_path_qs_ht_faults_status Motor Faults
Master Board Faults
3 Safety Core Fault
Definition Communication to the safety core has timed out after 100 ms.
Set condition The master board has detected a communication fault and has
timed out.
Clear condition Safety Core communication is re-established to the Master.
User action • Power cycle the unit.
• If problem persists, return the unit.
Motor Suspend Fault Yes
4 Auxiliary Core Fault
Definition Communication to the auxiliary core has communication issues
and has not received a response in 10 ms.
Set condition The master board has detected a communication fault and has
timed out.
Clear condition Aux Core communication is re-established to the Master.
User action • Power cycle the unit.
• If problem persists, return the unit.
Motor Suspend Fault No