Design Guidelines
Transport System Design
76 MagneMotion
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
Ground
Proper grounding of the QuickStick HT transport system is required to make sure of proper
operation and to minimize electrical safety issues.
• The bodies of the motors are grounded through the GND terminal on the motor.
• The QSMC and QSMC-2 are grounded through the GND stud on the motor control-
lers.
• The QSHT 5700 inverter is grounded through the GND stud on the inverter.
• The NC LITE is not grounded through its power connection. The case of the NC LITE
must be grounded to an electrical safety ground (PE) through the mounting features.
• The NC-12 is grounded through the GND stud on the node controller.
• The NC-E and NC-S are grounded through the power connection.
• All power supplies must be grounded to an electrical safety ground (PE) via the safety
ground in the AC input connector.
• All junction boxes must be grounded to an electrical safety ground (PE).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation MagneMotion QuickStick HT and is the answer not in the manual?

Rockwell Automation MagneMotion QuickStick HT Specifications

General IconGeneral
BrandRockwell Automation
ModelMagneMotion QuickStick HT
CategoryAccessories
LanguageEnglish

Related product manuals