E6582233
F-38
6
[Parameter setting]
Title Function Ad
ustment ran
e Default settin
PID control waiting time 0-2400 [s] 0
PID control 0: Disabled, 1: Enabled 0
Proportional gain 0.01-100.0 0.30
Integral gain 0.01-100.0 0.20
Differential gain 0.00-2.55 0.00
PID forward/reverse characteristics
selection
0: Forward
1: Reverse
0
1) External connection
2) Types of PID control interfaces
Set process amount input value (frequency setting) for when doing PID control.
Process amount input value
frequenc
settin
Feedback si
nal
Frequency setup mode selection:
1: Setting dial 1 (press in center to save)
2: Setting dial 2 (save even if power is off)
3: RS485 communication
5: UP/DOWN from external lo
ic inpu
External analog input
VI (DC: 4 - 20mA/
DC: 0 - 10V/
DC: 0 - 5V)
Preset-speed operation (, are all possible)
Note 1: Regarding setting value for : Terminal VI is used for a feed back signal, do not set
(terminal VI).
M
P
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
VI
CC
Pressure
transmitter
(1) Panel setting
(2) Internal preset-speed
setting
Feedback signals (1)DC : 4~20mA (2)DC : 0~10V (3)DC : 0~5V
(1) Panel keypad setting