E6582233
E-8
5
Note 1: The same characteristic can be obtained by setting the V/F control mode selection parameter  to
(automatic torque boost control) and the auto-tuning parameter  to (auto-tuning).
Refer to section 6.16
Note 2: Setting  to automatically programs  to .
2) When using vector control (increasing starting torque and high-precision
operations)
 is set to (Vector control + auto-tuning)
Setting torque boost setting macro function control  to (vector control + auto-tuning) provides high
starting torque bringing out the maximum in motor characteristics from the low-speed range. This suppresses
changes in motor speed caused by fluctuations in load to provide high precision operation. This is an
optimum feature for elevators and other load transporting machinery.
Note 1: The same characteristic can be obtained by setting the V/F control mode selection parameter
 to (vector control) and the auto-tuning parameter  to (auto-tuning).
Refer to section 6.16
Note 2: Setting  to automatically programs  to .
3) Energy-saving operation
 is set to (Energy saving + auto-tuning)
When torque boost setting macro function control  is set to (energy saving + auto-tuning), the
inverter always passes a current appropriate to the load for energy saving.
Note 1: The same characteristic can be obtained by setting the V/F control mode selection parameter
 to (automatic energy saving) and the auto-tuning parameter  to (auto-tuning).
Note 2: When  is set to ,  is automatically set to .
[Example of parameter setting]
Operation panel
action
LED display Operation

Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection  is set to
[Operation frequenc
y
]
)
 The first basic parameter “” (history function) is displayed.

Turn the setting dial to the right to change the parameter to 
(torque boost setting macro function).
Parameter values can be read by pressing the center of the setting
dial.
Turn the setting dial to the right to change the parameter to
(energy saving + auto-tuning). (Right side is the setting value, left
side is the histor
y
of the previous settin
g
.
)

Press the center of the setting dial to save the changed parameter.
 and the parameter are displayed alternately.
MODE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3E and is the answer not in the manual?

Toshiba TOSVERT VF-nC3E Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-nC3E
CategoryInverter
LanguageEnglish

Related product manuals