E6582233
G-7
7 7
7.2.2 Output terminal function (sink logic)
This function is used to output a variety of signals to external devices from the inverter.
With the logic output terminal function, you can select from multiple output terminal functions. Set two types of
functions for the OUT terminal and then you can output when either one or both of them is ON.
[Control terminal block]
OUT NO CC F R S1 S2 P24
FLA FLB FLC CC VI P5 FM
Usage
FLA, B, C function: Set at parameter .
OUT function: Set at parameter  and .
Note1) A chattering (momentary ON/OFF of contact) is generated by external factors of the vibration and the impact,
etc. In particular, please set the filter of 10ms or more, or timer for measures when connecting it directly with
input unit terminal of programmable controller. Please use the OUT terminal as much as possible when the
programmable controller is connected.
Assign one type of function to an output terminal
Terminal
s
y
mbol
Title Function Adjustment range Default setting
OUT

Output terminal selection 1A
0 - 255
4 (Low-speed detection signal)
FL
(
A, B, C
)

Output terminal selection 2
10 (Fault signal (trip output
))
Note 2) When assigning 1 type of function to the OUT terminal, set only .
Leave parameter  as the standard setting ( = ).
FLA
FLB
FLC
FL
OUT
NO

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3E and is the answer not in the manual?

Toshiba TOSVERT VF-nC3E Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-nC3E
CategoryInverter
LanguageEnglish

Related product manuals