E6582233
D-10
4
4.3.2 Return to default settings
: Default setting
Function
It is possible to return groups of parameters to their defaults, clear run times, and record/recall set
parameters.
[Parameter setting]
Title Function Ad
ustment ran
e Default settin
Default setting
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Load user setting parameters
9. Cumulative fan operation time
record clears
10 to 11: -
12: Number of startin
clea
0
★ This function will be displayed as 0 during reading on the right. This previous setting is displayed on the left.
Example:
★ cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50 Hz default setting (=)
Setting to sets the following parameters for base frequency 50 Hz use.
(The setting values of other parameters are not changed.)
Max. frequency () :50Hz Upper limit frequency () :50Hz
Base frequency 1 () :50Hz Base frequency 2 () :50Hz
VI input point 2 frequency () :50Hz Motor rated RPM () :1410 min
-1
60 Hz default setting (=)
Setting to sets the following parameters for base frequency 60 Hz use.
(The setting values of other parameters are not changed.)
Max. frequency () :60Hz Upper limit frequency () :60Hz
Base frequency 1 () :60Hz Base frequency 2 () :60Hz
VI input point 2 frequency () :60Hz Motor rated RPM () :1710 min
-1