6.3 MEMOBUS/Modbus Communications
226 YASKAWA SIEPC71061753C GA500 Technical Manual
Byte
Command Message Response Message (When Normal) Response Message (When There is a Fault)
Setting Data
(Hex.)
Setting Data
(Hex.)
Setting Data
(Hex.)
15 -
CRC-16
Upper AC -
16 - Lower D0
-
Note:
The number of bytes set in the command message set the data quantity × 2 during the command message.
Register status
bit 0 Data in register 1 selected with H5-25
1: Successfully read the register
0: Register read error
bit 1 Data in register 2 selected with H5-26
1: Successfully read the register
0: Register read error
bit 2 Data in register 3 selected with H5-27
1: Successfully read the register
0: Register read error
bit 3 Data in register 4 selected with H5-28
1: Successfully read the register
0: Register read error
bit 4 Not used
bit 5 Not used
bit 6 Not used
bit 7 Not used
Reading the Contents of Non-Consecutive Holding Registers
The drive uses function code 67 (Hex.) and subfunction code 010D (Hex.) to read data with a maximum of 120
holding registers.
You must give the holding register number from which to read separately.
Table 6.11 shows example messages when you read the frequency reference and torque limit from the drive for
slave 1. Table 6.11 uses this register data for the examples.
0024H: U1-01 [Frequency Reference] = 60.00 Hz (6000 = 1770H)
0028H: U1-09 [Torque Reference] = 100.0% (1000 = 03E8H)
Table 6.11 Message Example When Reading the Contents of Non-Consecutive Holding Registers
Byte
Command Message Response Message (When Normal) Response Message (When There is a Fault)
Setting Data
(Hex.)
Setting Data
(Hex.)
Setting Data
(Hex.)
0 Slave address 01 Slave address 01 Slave address 01
1 Function code 67 Function code 67 Function code E7
2
Subfunction
Code
Upper 01
Subfunction
Code
Upper 01 Error code 02
3 Lower 0D Lower 0D
CRC-16
Upper EA
4
Data Quantity
Upper 00
Byte No.
Upper 00 Lower 31
5 Lower 02 Lower 04 -
6
Holding register
1 No.
Upper 00
Holding register
1 data
Upper 17 -
7 Lower 24 Lower 70 -
8
Holding register
2 No.
Upper 00
Holding register
2 data
Upper 03 -
9 Lower 28 Lower E8 -
10
CRC-16
Upper 8B
CRC-16
Upper 47 -
11 Lower 29 Lower ED -
Note:
The number of bytes set in the command message set the data quantity × 2 during the command message.

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals