Troubleshooting
7
7.4 Fault
YASKAWA SIEPC71061753C GA500 Technical Manual 273
Code Name Causes Possible Solutions
Electrical interference caused a drive malfunction. Examine the control circuit lines, main circuit lines, and
ground wiring, and decrease the effects of electrical
interference.
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
The load inertia is set incorrectly. Examine the load inertia settings with KEB, overvoltage
suppression, or stall prevention during deceleration.
Adjust L3-25 [Load Inertia Ratio] to match the qualities of the
machine.
The Short Circuit Braking function used in OLV/
PM control method.
Connect a braking resistor to the drive.
There is motor hunting. Set n1-01 = 1 [Hunting Prevention Selection = Enabled] and
adjust n1-02 [Hunting Prevention Gain Setting].
Adjust n2-02 [Automatic Freq Regulator Time 1] and n2-03
[Automatic Freq Regulator Time 2].
Adjust n8-45 [Speed Feedback Detection Gain] and n8-47
[Pull-in Current Comp Filter Time].
Speed search does not complete at start when you
set A1-02 = 8 [EZ Vector Control] and use an
induction motor.
When E9-01 = 0 [Motor Type Selection = Induction (IM)], set b3-
24 = 2 [Speed Search Method Selection = Current Detection
Speed Search].
Note:
The drive detects this error if the DC bus voltage is more than the ov detection level while the drive is running.
The ov detection level is approximately 410 V with 200 V class drives. For 400 V class drives, the detection level is approximately 820 V.
Do a Fault Reset to clear the fault.
L5-08 [Fault Reset Enable Select Grp2] disables the Auto Restart function.
Code Name Causes Possible Solutions
PE1 PLC Faults
The communication option detected a fault. Refer to the manual for the communication option card.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
PE2 PLC Faults
The communication option detected a fault. Refer to the manual for the communication option card.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
PF Input Phase Loss
There is a phase loss in the drive input power. Correct errors with the wiring for main circuit drive input power.
There is loose wiring in the drive input power
terminals.
Tighten the terminal screws to the correct tightening torque.
The drive input power voltage is changing too
much.
Examine the input power for problems.
Make the drive input power stable.
If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
There is unsatisfactory balance between voltage
phases.
Examine the input power for problems.
Make the drive input power stable.
Set L8-05 = 0 [Input Phase Loss Protection Sel = Disabled].
The main circuit capacitors have become
unserviceable.
Examine the capacitor maintenance time in monitor U4-05
[CapacitorMaintenance]. If U4-05 is more than 90%, replace
the control board or the drive. For information about replacing
the control board, contact Yaskawa or your nearest sales
representative.
If drive input power is correct and the fault stays, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
Note:
The drive detects this error if the DC bus voltage changes irregularly without regeneration.
Do a Fault Reset to clear the fault.
Use L8-05 to enable and disable PF detection.
Code Name Causes Possible Solutions
PGo Encoder (PG) Feedback Loss
The holding brake is stopping the motor. Release the holding brake.
Note:
Do a Fault Reset to clear the fault.
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in F1-02 [PG Open Circuit Detection Select].

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals