EasyManuals Logo
Home>YASKAWA>Controller>CIPR-GA50C series

YASKAWA CIPR-GA50C series Technical Manual

YASKAWA CIPR-GA50C series
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #333 background imageLoading...
Page #333 background image
Specifications
10
10.4 Model Specifications (Three-Phase 200 V Class)
YASKAWA SIEPC71061753C GA500 Technical Manual 333
Model
2021 2030 2042 2056
Output
Rated Output Capacity
(kVA)
*3
HD 6.7 9.5 12.6 17.9
ND 8 11.4 16 21.3
Rated Output Current
(A)
HD 17.6 25.0 33.0 47.0
ND 21 30 42 56
Overload Tolerance
HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one
time each 10 minutes.
ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one
time each 10 minutes.
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
V/f, OLV, OLV/PM: 590 Hz
AOLV/PM: 270 Hz
EZOLV: 120 Hz
Measures for
Harmonics
DC reactor External options
Braking Device Braking Transistor Standard internal characteristics
EMC Filter
EMC Filter
IEC61800-3
Factory option
Models 2xxxE: Category C3 (Conducted emission)
Power Supply
Rated Voltage/Rated Frequency
Three-phase AC power supply 200 V to 240 V at 50/60 Hz
DC power supply 270 V to 340 V
Permitted Voltage Fluctuation -15% to +10%
Permitted Frequency Fluctuation ±5%
Input Power (kVA)
HD 8.7
11.0 17.0 24.0
ND 11
17.0 24.0 31.0
*1 The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2 The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3 The rated output capacity is calculated with a rated output voltage of 220 V.
Table 10.6 Ratings (Three-Phase 200 V Class)
Model
2070 2082
Maximum Applicable Motor Output (kW)
HD
*1
15 18.5
ND
*2
18.5 22
Maximum Applicable Motor Output (HP)
HD
*1
20 25
ND
*2
25 30
Input
Rated Input
Current (A)
HD (AC)
68 96
HD (DC)
83.3 117.6
ND (AC)
80 114
ND (DC)
98 139.6

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals